GrowattのハイブリットインバーターSPF 3000TL LVM-ESの設定です。(2022.10.6現在)
プログラム | 設定 |
1 Output source priority: To configure load power source priority | SBU |
2 Maximum charging current: set total charging current for solar and utility chargers. (Max. charging current = utility charging current + solar charging current) | 60A |
3 AC input voltage range | UPS |
4 Power saving mode enable/disable | Disable |
5 Battery type | US2 : User-Defined 2 (suitable when lithium battery without BMS communication) If “User-Defined 2” is selected, battery charge voltage and low DC cut-off voltage can be set up in program 19, 20 and 21. It is recommended to set to the same voltage in program 19 and 20(full charging voltage point of lithium battery). The inverter will stop charging when the battery voltage reaches this setting. |
6 Auto restart when overload occurs | Enable |
7 Auto restart when over temperature occurs | Enable |
8 Output voltage *This setting is only available when the inverter is in standby mode (Switch off). | 100 |
9 Output frequency *This setting is only available when the inverter is in standby mode (Switch off) | 50 |
10 Number of series batteries connected | 4 |
11 Maximum utility charging current Note: If setting value in Program 02 is smaller than that in Program 11, the inverter will apply charging current from Program 02 for utility charger | 5 |
12 Setting voltage point back to utility source when selecting “SBU priority” or “Solar first” in program 01 | 50 |
13 Setting voltage point back to battery mode when selecting “SBU priority” or “Solar first” in program 01 | 52 |
14 Charger source priority : To configure charger source priority | OSO : Only Solar |
15 Alarm control | Off |
16 Backlight control | On |
17 Beeps while primary source is interrupted | Off |
18 Overload bypass: When enabled, the unit will transfer to line mode if overload occurs in battery mode. | Disable |
19 C. V. charging voltage. If self-defined is selected in program 5, this program can be set up | 56.0V |
20 Floating charging voltage. If self-defined is selected in program 5, this program can be set up | 56.0V |
21 Low DC cut-off voltage. If self-defined is selected in program 5, this program can be set up. Low DC cut-off voltage will be fixed to setting value no matter what percentage of load is connected. | 48.0V |
28Address setting (for expansion) | 1 |
37-42 time-setting | (年月日時分秒の設定) |
43 Battery equalization | Disable (44-48は無効になります) |
44 Battery equalization voltage | 58.4 |
45 Battery equalized time | 60 |
46 Battery equalized timeout | 120 |
47 Equalization interval | 30 |
48 Equalization activated immediately | Off |
49 Utility charging time | 0000(default) Allow utility to charge the battery all day run. |
50 AC output time | 0000(default) Allow inverter to power the load all day run. |